The KL2702 output terminal uses an electronic load relay to switch a mains voltage of up to 230 V AC/DC. The switching element is a high-power MOSFET, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The KL2702 terminal has two independent outputs. Its signal state is indicated by means of light emitting diodes.
Technical data | KL2702 | KS2702 | KL2702-0020 | KL2702-0002 |
---|---|---|---|
Connection technology | 2-/3-/4-wire | ||
Number of outputs | 2 x make contacts | 2 x make contacts | 2 x make contacts, mutually locked |
Rated load voltage | 0…230 V AC/DC (DC…100 Hz) | ||
Load type | ohmic, inductive | ||
Max. output current | 0.3 A per channel, individually short-circuit-proof | 1.5 A steady load on each channel | 2 A steady load on each channel |
Frequency range | DC…100 Hz | ||
Surge voltage protection | from 400 V AC | ||
Peak current | 0.5 A (20 s), 1.5 A (100 ms) | 2.5 A (20 s), 7.5 A (100 ms) | 2.5 A (20 s), 7.5 A (100 ms) |
Contact resistance | 2.1 Ω typ., 3.2 Ω max. | 0.3 Ω typ., 0.4 Ω max. | 0.3 Ω typ., 0.4 Ω max. |
Switch-on time | 4…6 ms | 0.2…0.4 ms | 0.2…0.4 ms |
Switch-off time | 0.05…0.1 ms | 5…8 ms | 5…8 ms |
Switch-on delay | 320 µs | ||
Switch-off delay | 6.2 ms | ||
Max. residual voltage | (2.1 Ω) | (200 mΩ) | (300 mΩ) |
Electrical isolation | 500 V (K-bus/field voltage), 2500 V AC (1 min.) | ||
Leakage current (OFF state) | << 1 mA | ||
Current consumption power contacts | only leakage and load current | ||
Current consumption K-bus | typ. 10 mA | typ. 50 mA | typ. 50 mA |
Bit width in the process image | 2 outputs | ||
Configuration | no address or configuration setting | ||
Special features | – | – | |
Weight | approx. 55 g | ||
Operating/storage temperature | 0…+55 °C/-25…+85 °C | ||
Relative humidity | 95 %, no condensation | ||
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | ||
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | ||
Protect. class/installation pos. | IP 20/variable | ||
Pluggable wiring | for all KSxxxx Bus Terminals | – | – |
Approvals | CE, UL, Ex, GL | CE | CE |
![]() |
![]() |
![]() |
![]() |