Run LED1
Error LED1
+Input 1
-Input 1
Ground
Shield
Ground
Shield
Top view
Contact assembly
Run LED1
Error LED1
Run LED2
Error LED2
+Input 1
-Input 1
Ground
Shield
+Input 2
-Input 2
Ground
Shield
Top view
Contact assembly
KL3011, KL3012 | 1-, 2-channel analog input terminals 0…20 mA
The KL3011 and KL3012 analog input terminals handle signals in the range from 0 to 20 mA. The current is digitised to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device. The input channels of the Bus Terminals have differential inputs and possess a common, internal ground potential. The KL3011 is the single-channel variant and is characterised by its fine granularity and electrical isolation. The KL3012 combines two channels in one housing. An open lead or overload condition are detected, and the terminal status is relayed to the controller via the K-bus. The run LEDs give an indication of the data exchange with the Bus Coupler. The error LEDs indicate an overload condition and a broken wire.
| Technical data |
KL3011 | KS3011 |
KL3012 | KS3012 |
| Number of inputs |
1 |
2 |
| Power supply |
via the K-bus |
| Signal current |
0…20 mA |
| Technology |
differential input |
| Internal resistance |
80 Ω + 0.7 V |
| Common-mode voltage UCM |
35 V max. |
| Resolution |
12 bits |
| Conversion time |
~ 1 ms |
~ 2 ms |
| Measuring error |
< ±0.3 % (relative to full scale value) |
| Surge voltage resistance |
35 V DC |
| Electrical isolation |
500 V (K-bus/signal voltage) |
| Current consumption power contacts |
– (no power contacts) |
| Current consumpt. K-bus |
typ. 60 mA |
| Bit width in the process image |
input: 1 x 16 bit data (1 x 8 bit control/status optional) |
input: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Weight |
approx. 70 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
-25…+60 °C/-40…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all KSxxxx Bus Terminals |
| Approvals |
CE, UL, Ex, GL |
 |
 |
 |
| Special terminals |
|
| KL3012-0010 |
Siemens S5 format |
| KL3012-0011 |
altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA |
| KL3012-0012 |
fast µP, scan time approx. 0.5 ms |
| KL3012-0050 |
Siemens S7 format |