EIB/KNX Bus Terminal KL6301
Receive
EIB RxD/Power
Set
EIB Error 
Send 
EIB TxD 
Run 
Power contact
+24 V
Power contact 0 V
Set
EIB+
EIB-
Shield
Set
EIB+
EIB-
Shield
Top view 
Contact assembly 
extended shock and vibration range

KL6301 | EIB/KNX Bus Terminal

The KL6301 EIB/KNX Bus Terminal is integrated in an EIB/KNX network and can receive/transmit data from/to other EIB/KNX devices. Due to the integration in the Bus Terminal system, EIB/KNX components can also be integrated in higher-level bus systems such as Ethernet. The Bus Terminal is commissioned or configured via TwinCAT function blocks. Status LEDs directly indicate the bus status. The EIB/KNX terminal operates independent of the bus system used. Several KL6301 can be used with a single Bus Coupler or a Bus Terminal Controller. Up to 256 group addresses can be received; sending is only limited by the application.

Technical data KL6301
Technology EIB/KNX
Number of channels 1
Data transfer standard twisted pair (TP)
Connection 2-wire
Data transfer channels 1
Data transfer rates 9,600 baud
Bus access CSMA/CA
Cable length
Current consumpt. K-bus typ. 55 mA
Current consumption power contacts
Short-circuit-proof yes
Electrical isolation 500 V (K-bus/EIB)
Bit width in the process image input/output: 24 bytes
Configuration TwinCAT (function blocks)
Nominal voltage 24 V DC (-15 %/+20 %)
Input voltage 24 V DC (-15 %/+20 %)
Special features TwinCAT library: TwinCAT PLC EIB
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL, Ex
Accessories  
TwinCAT PLC EIB The library is installed free of charge together with TwinCAT from V2.11 Build 2229 (R3 and x64 engineering).
System  
subsystem For further subsystem products please see the system overview.