Terminal bus extension, coupler terminal KL9050
Power LEDs
K-bus
Coupler
terminal supply
Input for
power contacts
Power contacts
Matching resistor switch
Signal input
Terminal bus extension
Terminal bus run
Terminal bus error
Signal output
Terminal bus extension
Top view

KL9050 | Terminal bus extension, coupler terminal

The KL9050 coupler terminal replaces the Bus Coupler on a Bus Terminal block. The KL9050 is the counterpart to the KL9020. The S(F)TP cable (shielded twisted pair) is plugged into the upper socket, providing the logical connection to the Bus Coupler. The extension is fully transparent for the Bus Coupler. All Bus Terminal system functions remain unchanged. The second RJ45 socket allows the system to be extended further. A new KL9050 can be connected to the first coupler terminal. The whole system can thereby be extended by 31 stations. The supply voltage for the field level and the internal electronics can be input separately. Both levels are thereby electrically isolated from one another. In the KL9050 a 400 mA K-bus power supply unit supplies the added Bus Terminals. The internal electronics and the field level can be supplied together from a single voltage source. Three diagnostic LEDs give information about the supply voltage for each Bus Terminal block, internal and field level. The KL9050 can be used as the last coupler terminal in the system or as a bridge between two Bus Terminal blocks. You can switch between these two functions with a selector switch. The switch must be correctly positioned for the system to operate.

Technical data KL9050
Number of Bus Terminals 64
Current load ≤ 10 A
Power LED green
Defect LED
Type/number of peripheral signals Bus Coupler dependency
Distance between stations max. 5 m between KL9050 and KL9050
Bus interface 2 x RJ45 socket (input + output)
Power supply 24 V DC (-15 %/+20 %)
Input current 70 mA + (total K-bus current)/4, 200 mA max.
Starting current 2.5 x continuous current
Current consumption K-bus typ. 70 mA + (total K-bus current)/4, max. 200 mA
Current supply K-bus up to 400 mA
Power contacts 24 V DC max./10 A max.
Nominal voltage 24 V DC (-15 %/+20 %)
Electrical isolation 500 V (power contact/supply voltage/fieldbus)
PE contact yes
Shield connection
Electrical connection to DIN rail
Special features coupler terminal for K-bus extension (max. 64 Bus Terminals)
Weight approx. 75 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL, Ex, GL