4-channel relay module 230 V AC, 16 A KM2614
Top view

KM2614 | 4-channel relay module 230 V AC, 16 A

The KM2614 terminal module combines four pluggable power relays in one fieldbus module. The high switching capacity of 16 A at 230 V AC enables direct mains connection of consumers with high current consumption. The relays are positioned at the top and can therefore be exchanged easily. The KM2614 terminal module enables each relay to be manually switched to the ON status. A seal indicates the initial manual operation.

Technical data KM2614
Load type ohmic, inductive, lamp load
Max. output current 16 A
Number of outputs 4 x change-over
Operation automatic operation/manual operation at the relay
Nominal switching voltage 250 V AC, 30 V DC
Nominal switching current 16 A
Electrical isolation 1.5 kV (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 15 mA
Current consumption 24 V DC 50 mA for each active relay
Bit width in the process image 4 outputs
Switching current 16 A AC/12 A DC at 30 V DC
Operating cycles mech. (min.) 5 x 106
Operating cycles electr. (min.) 1 x 106 (1 A/250 V AC)
Lamp test, electronic ballast max. 25 A starting current
Minimum permitted load 5 mA (10 V DC)
Dimensions (W x H x D) 99 mm x 100 mm x 62 mm
Configuration no address or configuration setting
Special features automatic/manual operation at the relay
Weight approx. 250 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE
Further manual operating terminals
KM1644 4-channel manual operation
KM2604 4-channel relay module 230 V AC, 16 A, potential-free change-over contact
KM2642 2-channel relay module 230 V AC, 6 A, manual/automatic operation, relais state readable
KM2652 2-channel relay module 230 V AC, 6 A, manual/automatic operation, switch and relay state readable
KM4602 2-channel analog output terminal 0…10 V, manual/automatic operation
Accessories  
ZB2601 relay, 230 V AC, 16 A, coil 24 V, spare part KM2604
ZB2602 relay, manual operation, 230 V AC, 16 A, coil 24 V, spare part KM2614