CANopen master fieldbus connection CX1500-M510
Fieldbus connection
Address selector
Labelling area
Status LEDs
PC/104 interface
CANopen master

CX1500-M510 | CANopen master fieldbus connection

Technical data CX1500-M510
Fieldbus CANopen
Data transfer rates 10, 20, 50, 100, 125, 250, 500, 800, 1,000 kbaud
Bus interface open style connector, 5-pin
Bus device max. 127 slaves
Interface to the CPU ISA plug and play, 2 kbyte DPRAM
Max. power loss 1.8 W
Properties CANopen – supported PD communication types: event driven, time-controlled, synchronous, polling; emergency message handling, guarding and heartbeat, boot-up according to DS302, Online Bus Load Monitor and Bus Trace, the error management for each user is freely configurable.
Dimensions (W x H x D) 38 mm x 100 mm x 91 mm
Weight approx. 190 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protection class IP 20
System  
CANopen For further CANopen products please see the system overview.