Digital output
EPP2038-000x
 
EPP2038-0001 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 2 A (∑ 3&nbsp;A), with diagnostics
EPP2038-0001
Connector
assignment
I/O
connection
M8 I/O
connection sockets 
Signal status display
Labelling areas 
1 | + 24 V DC UP
3 | GNDP
4 | Output
1 | TX+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
3-wire  2-wire
EtherCAT P
signal input 
EtherCAT P
signal output 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
extended temperature range
EPP2038-0002 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 2 A (∑ 3&nbsp;A), with diagnostics
EPP2038-0002
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display
Labelling areas 
1 | + 24 V DC UP
2 | Output B
3 | GNDP
4 | Output A
5 | n.c.
1 | TX+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
3-wire  2-wire
EtherCAT P
signal input 
EtherCAT P
signal output 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
extended temperature range

EPP2038-000x | 8-channel digital output 24 V DC, IMAX = 2 A (∑ 3 A), with diagnostics

The EPP2038 EtherCAT P Box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 2 A each, although the total current is limited to 3 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 2 A signal current.

The signal state is indicated by means of light emitting diodes. The EPP2038 offers output diagnostics in the form of short circuit and open circuit detection per channel. The signals are optionally connected via M8 (EPP2038-0001) or M12 (EPP2038-0002) screw type connectors.

Technical data EPP2038-0001 EPP2038-0002
Number of outputs 8
Output connections M8, screw type M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type, EtherCAT-P-coded
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 2 A per channel, individually short-circuit-proof, total current max. 3 A
Short circuit current max. 7 A
Distributed clocks
Current consumption from US typ. 100 mA
Auxiliary power current typ. 20 mA + load
Diagnostics short-circuit, open load detection (min. load > 200 mA)
Power supply connection not necessary
Bit width in the process image 8 outputs + 8 diagnostic inputs
Electrical isolation 500 V
Weight approx. 165 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation
Accessories  
ZK700x-010x-0xxx Cables for EtherCAT P: Ultra-fast Communication and Power in One Cable
ZK2000-xxxx-xxxx Cables for M8 I/O connection sockets
ZK2000-6xxx-xxxx Cables for M12 I/O connection sockets