Digital output
EPP2816-00xx
 
EPP2816-0004 | 16-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A (∑ 3&nbsp;A)
EPP2816-0004
Connector
assignment
I/O
connection
M16, 19-pin
A-L| Output
 1…11
N-S| Output
 12…16
T| NC
M, U| GNDP
1 | TX+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
EtherCAT P
signal input 
EtherCAT P
signal output 
Signal status display 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
extended temperature range
EPP2816-0008 | 16-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A (∑ 3&nbsp;A)
EPP2816-0008
Connector
assignment
I/O
connection
D-sub, 25-pin
1-16 | Output
 1-16
17-22 | +24 V DC
 UP
23-25 | GNDP
1 | TX+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
EtherCAT P
signal input 
EtherCAT P
signal output 
Signal status display 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
extended temperature range
EPP2816-0010 | 16-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A (∑ 3&nbsp;A)
EPP2816-0010
Connector
assignment
I/O
connection
D-sub, 9-pin
1-8 | Output
9| GNDP
1 | TX+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
EtherCAT P
signal input 
EtherCAT P
signal output 
Signal status display 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
extended temperature range

EPP2816-00xx | 16-channel digital output 24 V DC, IMAX = 0.5 A (∑ 3 A)

The EPP2816 EtherCAT P Box with digital outputs connects the binary control signals from the controller on to the actuators at the process level. The sixteen outputs handle load currents of up to 0.5 A each, although the total current is limited to 3 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 0.5 A current. An output short-circuit is recognised and passed on to the controller.

The signal state is indicated in groups by means of light emitting diodes. The signal connection is realised by a 25-pin D-sub socket (EPP2816-0008). The EPP2816 is thus ideally suited for multi-pin connector valve terminals. All outputs are short-circuit-proof, protected against inverse connection and can be diagnosed.

Technical data EPP2816-0004 EPP2816-0008 EPP2816-0010
Number of outputs 16
Output connections M16, 19-pin D-sub socket, 25-pin 2 x D-sub socket, 9-pin
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type, EtherCAT-P-coded
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof, total current max. 3 A
Short circuit current max. 1.5 A
Distributed clocks yes
Current consumption from US typ. 100 mA
Auxiliary power current typ. 20 mA + load
Power supply connection not necessary
Bit width in the process image 16 outputs, 16 inputs (diagnostics)
Electrical isolation 500 V
Special features ideal for multi-pin connector valve terminals
Weight approx. 165 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation