2-channel pulse width current terminals 24 V DC EL2535
Error B LED
Warning
Enable B LED
Power LED
Error A LED 
Enable A LED 
E-bus Run LED 
Power contact
+24 V
Power contact 0 V
A1
B1
GNDA
E1
A2
B2
GNDB
E2
Top view 
Contact assembly 
extended shock and vibration range

EL2535 | 2-channel pulse width current terminals 24 V DC

The EL2535, EL2535-0050 and EL2535-0002 output terminals control the output current via pulse width control of the supply voltage. They are galvanically isolated from the E-bus. The current value 0 up to maximum output current (±1 A, ±50 mA, ±2 A) is specified by the automation device via a 16 bit value. The output stages are protected against overload and short-circuit. The EtherCAT Terminals have two channels that indicate their signal state via light emitting diodes. The LEDs simplify local diagnosis by displaying typical load and wiring faults.

Technical data EL2535 | ES2535 EL2535-0002 EL2535-0050
Connection technology PWM output, push-pull outputs
Number of outputs 2
Rated load voltage 24 V DC (-15 %/+20 %)
Load type inductive > 1 mH
Distributed clocks
Max. output current ±1 A per channel ±2 A ±50 mA
Short circuit current typ. < 2 A < 4 A typ. < 500 mA typ.
PWM clock frequency 30 kHz default
Duty factor 0…100 % (current-controlled)
Resolution 10 bit
Reverse voltage protection yes
Current consumption E-bus typ. 110 mA
Electrical isolation 500 V (E-bus/field potential)
Current consumption power contacts typ. 30 mA + load
Bit width in the process image 48 inputs/outputs: 2 x 16 bit data, 2 x 8 bit control/status
Special features 2 digital 24 V inputs
Weight approx. 50 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Pluggable wiring for all ESxxxx terminals
Approvals CE CE CE, Ex