2-channel relay output terminal 230 V AC/300 V DC, 1 A EL2652
Signal LED 2
Signal LED 1 
Output 1
230 V
Output 1
Output 2
230 V AC
Output 2
Top view 
Contact assembly 

EL2652 | 2-channel relay output terminal 230 V AC/300 V DC, 1 A

The EL2652 output terminal has two relays, each featuring a change-over contact. The relay contact can be used universally for switching devices requiring mains power up to 230 V AC or 300 V DC. The EL2652 is equipped with potential-free contacts. The signal state of the EtherCAT Terminal is indicated via LEDs.

Technical data EL2652 | ES2652
Connection technology relay output
Number of outputs 2 x change-over
Switching voltage max. 250 V AC, 300 V DC
Nominal voltage 230 V AC (max. switching voltage 250 V AC/300 V DC)
Load type ohmic, inductive, lamp load
Distributed clocks
Minimum permitted load 100 mA (12 V DC)
Current consumption E-bus 180 mA
Electrical isolation 1.5 kV (E-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III
Current consumption power contacts
Switching frequency max. 6/min. (at rated load)
Operating cycles mech. (min.) 5 x 106
Operating cycles electr. (min.) 1 x 106 (1 A/250 V AC ohmic load)
Special features reverse switching realisable
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Approvals CE, UL