2-channel triac output terminal EL2712
Signal LED 2
Signal LED 1 
Power contact
230 V
Power contact N
Power contact PE
Output 1
Output 2
230 V
N
PE
Top view 
Contact assembly 

EL2712 | 2-channel triac output terminal

The EL2712 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two independent outputs and indicates its signal state by means of light emitting diodes.

Technical data EL2712 | ES2712
Connection technology triac output, 2-wire
Number of outputs 2 x make contacts
Rated load voltage 12…230 V AC
Load type ohmic, inductive
Distributed clocks
Max. output current 0.5 A per channel
Switching times in zero crossing, 0.1…10 ms
Frequency range 47…63 Hz
Surge voltage protection > 275 V
Peak current 40 A (16 ms), 1.5 A (30 s)
Standby current 0.6 mA
Leakage current (OFF state) typ. 0.8 mA, max. 1.5 mA
Switch-on time 0.1…10 ms, zero crossing
Switch-off time T/2
Max. residual voltage 1.5 V (60 mA…1 A), 150 Ω (< 60 mA)
Current consumption E-bus typ. 120 mA
Electrical isolation 500 V (E-bus/field voltage), 3750 V AC (1 min.)
Current consumption power contacts
Bit width in the process image 2 outputs
Configuration no address or configuration setting
Special features suitable for conventional blind motors
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Product announcement
estimated market release on request