EL3042 | 2-channel analog input terminal 0…20 mA, single-ended, 12 bit

The job of the EL3042 analog input terminal is to supply power to measuring transducers located in the field, and to transmit analog measurement signals with electrical isolation to the automation device. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a supply terminal (EL9xxx) with electrical isolation. The input electronics is independent of the supply voltage of the power contacts. The 0 V power contact is the reference potential for the inputs. The EtherCAT Terminal indicates its signal state by means of light emitting diodes.

Technical data EL3042 | ES3042
Number of inputs 2 (single-ended)
Power supply via the E-bus
Technology single-ended
Signal current 0…20 mA
Distributed clocks
Internal resistance 85 Ω typ.
Input filter limit frequency 1 kHz
Dielectric strength max. 30 V
Conversion time 0.625 ms default setting, configurable
Resolution 12 bit (16 bit presentation, incl. sign)
Measuring error < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bus typ. 130 mA
Bit width in the process image inputs: 8 byte
Special features standard and compact process image, activatable FIR/IIR filters, limit value monitoring
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Approvals CE, UL, Ex
Special terminals
EL3142-0010 signal current ±10 mA