4-channel thermocouple input terminal with open-circuit recognition EL3314
Error LED 4
Error LED 3
Error LED2
Error LED 1
Run LED 4 
Run LED 3 
Run LED 2 
Run LED 1 
Power contact
+24 V
Power contact 0 V
+TC1
+TC2
+TC3
+TC4
-TC1
-TC2
-TC3
-TC4
Top view 
Contact assembly 
Observe for earthed
thermocoupler:
differential inputs
max. ± 2 V to ground
extended temperature range
extended shock and vibration range

EL3314 | 4-channel thermocouple input terminal with open-circuit recognition

The EL3314 analog input terminal allows four thermocouples to be connected directly. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3314 can also be used for mV measurement.

Technical data EL3314
Number of inputs 4
Power supply via the E-bus
Thermocouple sensor types types K, J, L, E, T, N, U, B, R, S, C (default setting type K), mV measurement
Distributed clocks
Input filter limit frequency typ. 1 kHz; dependent on sensor length, conversion time, sensor type
Connection method 2-wire
Wiring fail indication yes
Conversion time approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Temperature range in the range defined in each case for the sensor (default setting: type K; -200…+1370 °C); voltage measurement: ±30 mV…±75 mV
Resolution 0.1 °C per digit
Measuring error < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bus typ. 200 mA
Bit width in the process image 4 x 32 bit TC input, 4 x 16 bit TC output
Configuration no address setting, configuration via the controller
Special features open-circuit recognition
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL, Ex
Related products  
EL3314-0010 4-channel thermocouple input terminal, high-precision, with open-circuit recognition
EL3314-0020 4-channel thermocouple input terminal, high-precision, with open-circuit recognition, with calibration certificate
EL3314-0090 4-channel thermocouple input, 16 bit, TwinSAFE SC