1-channel precise load cell analysis (resistor bridge), 24 bit EL3356-0010
Error Ref.
Self test
Measure
Power LED
Error Diff. 
Self calibration 
Steady state 
Run LED 
Power contact
+UV
Power contact 0 V
+UD
-UD
-Uv
Shield
+UREF
-UREF
+Uv
Shield
Top view 
Contact assembly 
The supply voltage UV has
to be supplied from an
external source, max. 12 V,
e.g. EL9510.

EL3356-0010 | 1-channel precise load cell analysis (resistor bridge), 24 bit

Technical data EL3356-0010
Number of inputs 2, for 1 resistor bridge in full bridge technology
Technology resistor bridge, strain gauge
Distributed clocks yes
Measuring range UD max. -25…+25 mV rated voltage
Measuring range UREF max. -12…+12 V rated voltage
Internal resistance > 200 kΩ (UREF), > 1 MΩ (UD)
Input filter limit frequency 10 kHz low pass (-3 dB)
Conversion rate 10,000…4 samples/s (0.1…250 ms conversion time)
Power supply UV up to 12 V from power contacts, dependent on sensor
Resolution 24 bits, 32 bits presentation
Measuring error < ±0,01 % for the calculated load value
in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active
Current consumption power contacts depends on strain gauge supply, min. 1 mA
Current consumption E-bus typ. 280 mA
Supported nominal sensitivity all, resolution of parameter: 0.01 µV/V
recommended: 0.5…4 mV/V
Special features auto-calibration, quadruple averager, dynamic filters
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable