2-channel analog input terminal ±10 V, ±5 V, ±2.5 V, ±1.25 V, differential input, 24 bit EL3602
Error LED2
Run LED2
Error LED1 
Run LED1 
Power contact
+24 V
Power contact 0 V
+Input 1
-Input 1
GND
Shield
+Input 2
-Input 2
GND
Shield
Top view 
Contact assembly 
extended temperature range
extended shock and vibration range

EL3602 | 2-channel analog input terminal ±10 V, ±5 V, ±2.5 V, ±1.25 V, differential input, 24 bit

The EL3602 analog input terminal handles signals in the ranges ±10 V, ±5 V, ±2.5 V and ±1.25 V. The voltage is digitised to a resolution of 24 bits, and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a common, internal ground potential. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical data EL3602 | ES3602
Number of inputs 2 (differential)
Power supply via the E-bus
Technology differential input
Signal voltage -10…+10 V, -5…+5 V, -2.5…+2.5 V, -1.25…+1.25 V (parameterisable)
Oversampling factor
Distributed clocks
Distributed clock precision
Internal resistance > 200 kΩ
Input filter limit frequency 3 kHz
Common-mode voltage UCM 35 V max.
Resolution 24 bit (incl. sign)
Conversion time 20 ms default setting, 1…400 ms configurable
Input signal bandwidth
Measuring error < ±0.01 % at 25 °C, 50 Hz filter (relative to full scale value)
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bus typ. 190 mA
Crosstalk attenuation > 60 dB
Special features various filter times, limit value monitoring, high precision
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Approvals CE, UL, Ex
Related products  
EL3602-0002 2-channel analog input terminal, ±200 mV, differential input, 24 bit
EL3602-0010 signal voltage -75…+75 mV, measuring error < ±0.05 % at 25 °C (relative to full scale value, 50 Hz filter)
EL3602-0020 2-channel analog input terminal ±10 V, ±5 V, ±2.5 V, ±1.25 V, differential input, 24 bit, with calibration certificate