2-channel analog output terminal 0…10 V, 16 bit EL4102
Run LED2
Run LED1 
Power contact
+24 V
Power contact 0 V
Output 1
GND
Shield
Output 2
Top view 
Contact assembly 
extended temperature range
extended shock and vibration range

EL4102 | 2-channel analog output terminal 0…10 V, 16 bit

The EL4102 analog output terminal generates signals in the range between 0 and 10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels of the EtherCAT Terminal have a common ground potential. The EL4102 combines two channels in one housing. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.

Technical data EL4102 | ES4102
Connection technology 2-wire, single-ended
Number of outputs 2
Power supply via the E-bus
Signal voltage 0…10 V
Distributed clocks yes
Distributed clock precision << 1 µs
Load > 5 kΩ (short-circuit-proof)
Output error < 0.1 % (relative to end value)
Resolution 16 bit (incl. sign)
Electrical isolation 500 V (E-bus/signal voltage)
Conversion time ~ 40 µs
Current consumption power contacts
Current consumption E-bus typ. 210 mA
Bit width in the process image 2 x 16 bit AO output
Special features Watchdog parameterisable; user synchronisation can be activated.
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Approvals CE, UL, Ex