TwinSAFE SC: IO-Link terminal EL6224-0090
Run LEDs
1, 3, 5, 7
Status LEDs
9, 11, 13, 15
Power contact
+24 V
Power contact 0 V
Input 1 
+24 V 
Input 2 
+24 V 
Input 3 
+24 V 
Input 4 
+24 V 
+24 V
0 V
+24 V
0 V
+24 V
0 V
+24 V
0 V
Top view 
Contact assembly 

EL6224-0090 | TwinSAFE SC: IO-Link terminal

The EL6224-0090 IO-Link terminal enables connection of up to four IO-Link devices, e.g. actuators, sensors or combinations of both. The parameterisation of the IO-Link devices with service data can be done from TwinCAT via ADS or very conveniently via the integrated IO-Link configuration tool.IO-Link devices can be operated in 3-wire connection mode.

With the aid of the TwinSAFE SC technology (TwinSAFE Single Channel) it is possible to make use of standard signals for safety tasks in any network or fieldbus. The standard functions and features of the I/Os remain available. The data from these TwinSAFE SC I/Os is fed to the TwinSAFE Logic, where they undergo safety-related multi-channel processing. In the Safety Logic the data originating from different sources is analysed, checked for plausibility and submitted to a “voting”. This is done by certified function blocks such as Scale, Compare/Voting (1oo2, 2oo3, 3oo5), Limit, etc. For safety reasons, however, at least one of the data sources must be a TwinSAFE SC component. The remainder of the data can originate from other standard Bus Terminals, drive controllers or measuring transducers.

With the aid of the TwinSAFE SC technology it is typically possible to achieve a safety level equivalent to PL d/Cat. 3 in accordance with EN ISO 13849-1 or SIL 2 in accordance with EN 62061.

Technical data EL6224-0090
Technology IO-Link input/output
Specification version IO-Link V1.1
IO-Link interfaces 4
Field voltage 24 V DC via power contacts
Connection 3-wire
Data transfer rates 4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Cable length max. 20 m
Power supply via E-bus and power contacts
Electrical isolation 500 V (E-bus/signal voltage)
Power contacts yes
Supply current for devices 500 mA per device
Current consumption E-bus typ. 120 mA
Special features TwinSAFE SC, each channel parameterisable in TwinCAT
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL
Further information
TwinSAFE SC TwinSAFE SC technology
Related products  
EK1960 TwinSAFE Compact Controller
EL6910 TwinSAFE Logic
System  
IO-Link For further IO-Link products please see the system overview.