Potential supply terminal, 24 V DC, with diagnostics and fuse EL9210
Error LED
Power LED
Power contact
Power contact
Power contact
Infeed 24 V
Infeed 0 V
PE
Top view 
Contact assembly 

EL9210 | Potential supply terminal, 24 V DC, with diagnostics and fuse

The EL9210 power feed terminal makes it possible to set up various potential groups with the standard voltage of 24 V DC. In order to monitor the supply voltage, the terminals with diagnostics function report the status of the power feed terminal to the EtherCAT Coupler through two input bits. It is thus possible for the controller to check the distributed peripheral voltage over the fieldbus.

Technical data EL9210
Technology potential supply terminal with diagnostics and fuse
Current load ≤ 10 A
Power LED green
Defect LED red
Renewed infeed yes
Current consumption E-bus typ. 90 mA
Nominal voltage 24 V DC
Integrated fine-wire fuse …6.3 A
Electrical isolation 500 V (E-bus/field potential)
Diagnostics in the process image yes
Reported to E-bus yes
PE contact yes
Shield connection
Connection facility to additional power contact 1
Bit width in the process image 2
Electrical connection to DIN rail
Housing width in mm 12
Side by side mounting on
EtherCAT Terminals with
power contact
yes
Side by side mounting on
EtherCAT Terminals without
power contact
yes
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Approvals CE, UL, Ex