Power supply terminal for E-bus, with diagnostics ELM9410

ELM9410 | Power supply terminal for E-bus, with diagnostics

The ELM9410 power supply terminal is used to increase the E-bus current. The exchange of data between EtherCAT Couplers and the connected EtherCAT Terminals takes place over the E-bus. Each EtherCAT Terminal requires a certain amount of current from the E-bus (see technical data: “Current consumption via E-bus“). This current is fed into the E-bus by the power supply unit of the respective EtherCAT Coupler. In configurations with a large number of EtherCAT Terminals, the ELM9410 can be used to increase the current supply to the E-bus by 2 A. The ELM9410 is designed in particular to meet the needs of high-precision analog measurement technology, e.g. with ELM3xxx terminals: to reduce interference in the connected measurement technology, both the E-bus supply US and the 24 V power contact supply UP are electrically isolated and filtered in the terminal. The power contact supply can carry a maximum load of 2 A. The extensive voltage and temperature monitoring provides assistance with commissioning and operation; results are displayed by LED and in the process image. As a result, the ELM9410 can be used in special measuring situations instead of the conventional EL9410 supply. Mixed operation with EK1100/EL9410 is possible, however, not ensuring electrical isolation in this configuration.

Technical data ELM9410
Technology power supply terminal
Short-circuit-proof yes
Input voltage 24 V DC
Input current typ. 70 mA + (E-bus/4)
Power supply 24 V DC (-15 %/+20 %)
Output voltage 5 V for E-bus supply
Output current 2 A
Current consumption E-bus
Current consumption from US 50 mA + (∑ E-bus current/4)
Current consumption from UP 50 mA + load
Current supply E-bus 2000 mA
Insulation voltage input/output 500 V (E-bus/US/UP)
Power contacts max. 24 V DC/max. 2 A
Diagnostics in the process image yes
Special features electrically isolated output voltages, reverse polarity protection, diagnostics of supply and output voltages
Weight approx. 450 g
Operating/storage temperature 0…+60 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Electrical isolation 500 V (E-bus/field potential)
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE