Signal LED 2
Signal LED 1
Power contact
+24 V EX
Power contact
0 V EX
+Output 1
-Output 1
+Output 2
-Output 2
Top view
ELX2002 | 2-channel digital output terminal 24 V DC, 45 mA, Ex i
The ELX2002 digital output terminal enables the direct connection of intrinsically safe actuators located in hazardous areas classified Zone 0/20 or 1/21. The ELX2002 supplies an output voltage of 24 V DC and a maximum output current of 45 mA per channel, total current is 80 mA. The signal state of the EtherCAT Terminal is indicated by a light emitting diode.
Technical data |
ELX2002 |
Technology |
intrinsically safe actuators |
Connection technology |
2-wire |
Number of outputs |
2 |
Rated load voltage |
24 V DC, Ri = 254 Ω |
Load type |
ohmic, inductive, capacitive |
Max. output current |
45 mA per channel, ∑ 80 mA |
Current consumption power contacts |
typ. 10 mA + load |
Current consumption E-bus |
typ. 45 mA |
Weight |
approx. 55 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. |
IP 20/see documentation |
Approvals |
CE, Ex, IECEx |
 |
 |
further Ex components |
|
ELXxxxx |
EtherCAT Terminals with intrinsic safe in- and output |
ELXxxxx-0090 |
EtherCAT Terminals with intrinsic safe in- and output and TwinSAFE SC |
CPXxxxx |
Multi-touch Panel PCs and multi-touch Control Panels for use in hazardous areas, Zone 2/22 |
 |
 |