2-channel digital output terminal 24 V DC, 40 mA, Ex i ELX2002
Signal LED 2
Signal LED 1 
Power contact
+24 V EX
Power contact
0 V EX
+Output 1
-Output 1
+Output 2
-Output 2
Top view 
extended temperature range
extended shock and vibration range

ELX2002 | 2-channel digital output terminal 24 V DC, 40 mA, Ex i

ExThe ELX2002 digital output terminal enables the direct connection of intrinsically safe actuators located in hazardous areas classified Zone 0/20 or 1/21. The ELX2002 supplies an output voltage of 24 V DC and a maximum output current of 40 mA per channel, total current is 80 mA. The signal state of the EtherCAT Terminal is indicated by a light emitting diode.

Technical data ELX2002 | ESX2002
Technology intrinsically safe actuators
Connection technology 2-wire
Number of outputs 2
Rated load voltage 24 V DC, Ri = 254 Ω
Load type ohmic, inductive, capacitive
Max. output current 45 mA per channel, ∑ 80 mA
Current consumption power contacts typ. 10 mA + load
Current consumption E-bus typ. 45 mA
Electrical isolation 2500 V (E-bus/field potential)
Weight approx. 55 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Pluggable wiring for all ESXxxxx terminals
Approvals CE, Ex (certification pending)
further Ex components  
ELXxxxx EtherCAT Terminals with intrinsic safe in- and output
CPXxxxx Multi-touch Panel PCs and multi-touch Control Panels for use in hazardous areas, Zone 2/22
Product announcement
estimated market release 4th quarter 2017