4-channel analog input terminal thermocouple/mV measurement, 2-wire connection, 16 bit, Ex i ELX3314
Error LED 4
Error LED 3
Error LED 2
Error LED 1
Run LED 
Power contact
+24 V EX
Power contact
0 V EX
+TC1
+TC2
+TC3
+TC4
-TC1
-TC2
-TC3
-TC4
Top view 
extended temperature range

ELX3314 | 4-channel analog input terminal thermocouple/mV measurement, 2-wire connection, 16 bit, Ex i

ExThe ELX3314 analog input terminals allows the direct connection of thermocouples located in hazardous areas classified Zone 0/20 or 1/21. The circuitry of the ELX3314 can operate sensors with 2-wire technology. Linearisation is possible over the entire freely selectable temperature range. The error LEDs indicate a broken wire. Compensation for the cold junction is achieved through internal temperature measurement. Millivolt measurement is also possible with ELX3314.

Technical data ELX3314
Technology temperature measurement
Sensor types thermocouples type K, J, L, E, T, N, U, B, R, S, C (default: type K)
Number of inputs 4 (differential)
Connection method 2-wire
Measuring range depending on sensor type, default type K: -200…+1350 °C, voltage measurement: ±30…±100 mV, for further types and details see documentation
Resolution 0.1 °C per digit
Measuring error < ±0.3 % (relative to full scale value)
Internal resistance typ. ≥ 10 kΩ (differential)
Input filter limit frequency typ. 1 kHz; depending on sensor length, conversion time, sensor type
Conversion time 10…800 ms (adjustable, default: 100 ms)
Supply voltage electronics 24 V DC (via power contacts), ELX9560 power supply
Current consumption power contacts typ. 10 mA
Current consumption E-bus typ. 70 mA
Special features limit value monitoring, digital filter and characteristic curve linearisation integrated
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Approvals CE, Ex, IECEx
further Ex components  
ELXxxxx EtherCAT Terminals with intrinsic safe in- and output
ELXxxxx-0090 EtherCAT Terminals with intrinsic safe in- and output and TwinSAFE SC
CPXxxxx Multi-touch Panel PCs and multi-touch Control Panels for use in hazardous areas, Zone 2/22