Digital input
EP1008-000x
EP1008-0001
EP1008-0002
Connector
assignment
I/O
connection
M8 I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
M12
1 | + 24 V DC Us
3 | GND
4 | Input
1 | + 24 V DC Us
2 | Input B
3 | GND
4 | Input A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire 2-wire
Power supply feed
Power supply down-
stream connection
EtherCAT
signal input
EtherCAT
signal output
EP1008-000x | 8-channel digital input 24 V DC, 3.0 ms
The EP1008 EtherCAT Box with digital inputs acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the controller. The state of the signals is indicated by light emitting diodes. The signals are optionally connected via M8 (EP1008-0001) or M12 (EP1008-0002) screw type connectors.
The sensors are supplied from the box supply voltage US. The auxiliary voltage UP is not used in the input module, but may be connected in order to be relayed downstream.
Technical data |
EP1008-0001 |
EP1008-0002 |
Specification |
EN 61131-2, type 1/3 |
Number of inputs |
8 |
Input connections |
M8, screw type |
M12, screw type |
Protocol |
EtherCAT |
Bus interface |
2 x M8 socket, shielded, screw type |
Nominal input voltage |
24 V DC (-15 %/+20 %) |
Input filter |
3 ms |
“0“ signal voltage |
-3…+5 V (EN 61131-2, type 3) |
“1“ signal voltage |
11…30 V (EN 61131-2, type 3) |
Input current |
typ. 3 mA (EN 61131-2, type 3) |
Distributed clocks |
– |
Sensor supply |
from control voltage, max. 0.5 A total, short-circuit-proof |
Power supply connection |
feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Bit width in the process image |
8 inputs |
Current consumption from US |
120 mA |
Electrical isolation |
500 V |
Weight |
approx. 165 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. |
IP 65/66/67 (conforms to EN 60529)/variable |
Approvals |
CE, UL, Ex |
 |
 |
 |
Related products |
|
EQ1008-0002 |
EtherCAT Box, stainless steel housing, 8 digital inputs, 24 V DC, filter 3.0 ms |
 |
 |