Communication
EP6228
 
EP6228-0022 | 8-channel IO-Link master
EP6228-0022
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
EtherCAT
signal input 
EtherCAT
signal output 
1 | L+
2 | NC
3 | L-
4 | C/Q
5 | NC
extended temperature range
EP6228-3032 | 8-channel IO-Link master
EP6228-3032
Connector
assignment
I/O
connection
M12 I/O
connection sockets  
Signal status display
Labelling areas 
Power OUT 
Power IN 
1 | L+
2 | P24
3 | L-
4 | C/Q
5 | N24
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | GNDP
2 | GNDs
3 | FE
4 | + 24 V DC US
5 | + 24 V DC UP
3-wire
EtherCATs
signal input 
EtherCAT signal output 
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
extended temperature range

EP6228 | 8-channel IO-Link master

The EP6228 IO-Link module enables connection of up to eight IO-Link devices, e.g. IO-Link box modules, actuators, sensors or combinations thereof. A point-to-point connection is used between the module and the device. The terminal is parameterised via the EtherCAT master. IO-Link is designed as an intelligent link between the fieldbus level and the sensor, wherein parameterisation information can be exchanged bidirectionally via the IO-Link connection. The parameterisation of the IO-Link devices with service data can be done from TwinCAT via ADS or very conveniently via the integrated IO-Link configuration tool.

In the standard setting, the EP6228 functions as a 8-channel input terminal, 24 V DC, which communicates with connected IO-Link devices, parameterises them and, if necessary, changes their operating mode.

Technical data EP6228-0022 EP6228-3032
Data transfer rates 4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Connection method M12, screw type
Specification version IO-Link V1.1, Class A IO-Link V1.1, Class B
IO-Link interfaces 8
Nominal voltage 24 V DC (-15 %/+20 %)
Distributed clocks yes
Cable length max. 20 m
IO-Link sensor supply L+ 24 V DC, 0.7 A per port, ∑ 4 A for 8 ports 24 V DC, 1.4 A per port, ∑ 11.2 A
IO-Link sensor supply 2L+ 24 V DC, max. 4.0 A per port, ∑ 4.0 A for each 2 ports
Current consumption from US typ. 130 mA + load
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin feed: 1 x 7/8" plug, 5-pin; downstream connection: 1 x 7/8" socket, 5-pin
Electrical isolation 500 V
Weight approx. 250 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL CE, UL in preparation
Accessories  
ZK1090-3xxx-xxxx Cables for EtherCAT signal in- and -output
ZK2020-3xxx-xxxx Cables for M8 power supply
Related products
EP6224 EtherCAT Box, industrial housing, 4-channel IO-Link master, IP 67
EPP6228 EtherCAT P Box, industrial housing, 8-channel IO-Link master, IP 67
EL6224 EtherCAT Terminal, IO-Link master, IP 20
KL6224 Bus Terminal, IO-Link master, IP 20
EPIxxxx, ERIxxxx IO-Link box modules, IP 67
System  
IO-Link For further IO-Link products please see the system overview.