Digital output
EQ2008-0002
 
EQ2008-0002 | 8-channel digital output 24 V DC
EQ2008-0002
Connector
assignment
I/O
connection
M12 I/O
connection socket
Signal status display
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
1 | + 24 V DC Us
2 | Output B
3 | GND
4 | Output A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
Power supply feed
Power supply down-
stream connection
EtherCAT
signal input
EtherCAT
signal output
extended temperature range

EQ2008-0002 | 8-channel digital output 24 V DC

The EQ2008 EtherCAT Box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A and indicate their status through light emitting diodes. The signals are connected via M12 screw type connectors. The outputs are short-circuit-proof and protected against inverse connection.

The modules of the EQxxxx series are made of stainless steel and feature the “Hygienic Design” completely. Therefore they are ideal for applications in the food, chemical or pharmaceutical industries, which require protection class IP 69K.

Technical data EQ2008-0002
Number of outputs 8
Rated load voltage 24 V DC (-15 %/+20 %)
Output connections M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof, total current max. 4 A
Short circuit current typ. 1.5 A
Distributed clocks
Auxiliary power current typ. 20 mA + load
Current consumption from US (without sensor current) 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 outputs
Electrical isolation 500 V
Special features V2A stainless steel, Hygienic Design
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 69K (according to EN 60529)/variable
Approvals CE, UL
Accessories  
ZK1090-3xxx-xxxx Cables for EtherCAT signal in- and -output
ZK2000-6xxx-xxxx Cables for M12 I/O connection sockets
ZK2020-3xxx-xxxx Cables for M8 power supply
Stainless steel products  
For further information on the stainless steel control solution please see here.