Digital input
ER1008-0022
 
ER1008-0022 | 8-channel digital input 24 V DC, 3.0 ms filter
ER1008-0022
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC Us
2 | n.c.
3 | GND
4 | Input A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
extended temperature range

ER1008-0022 | 8-channel digital input 24 V DC, 3.0 ms filter

The ER1008-0022 EtherCAT Box with digital inputs acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the controller. The state of the signals is indicated by light emitting diodes. The signals are connected via M12 screw type connectors.

The sensors are supplied from the box supply voltage US. The auxiliary voltage UP is not used in the input module, but may be connected in order to be relayed downstream.

The EtherCAT Box modules with zinc die-cast housing are ready for use in harsh industrial and process environments. With the fully sealed design and metal surfaces the ER series is ideal for applications requiring enhanced load capacity and protection against weld spatter, for example.

Technical data ER1008-0022
Specification EN 61131-2, type 1/3
Number of inputs 8
Input connections M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type
Nominal input voltage 24 V DC (-15 %/+20 %)
Input filter 3.0 ms
“0“ signal voltage -3…+5 V (EN 61131-2, type 3)
“1“ signal voltage 11…30 V (EN 61131-2, type 3)
Input current typ. 3 mA (EN 61131-2, type 3)
Distributed clocks
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 inputs
Current consumption from US (without sensor current) 120 mA
Electrical isolation 500 V
Special features 1 input per M12 plug
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation
Accessories  
ZK1090-3xxx-xxxx Cables for EtherCAT signal in- and -output
ZK2000-6xxx-xxxx Cables for M12 I/O connection sockets
ZK2020-3xxx-xxxx Cables for M8 power supply
Related products  