Digital output
ER2008-0022
 
ER2008-0022 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A (∑ 4 A)
ER2008-0022
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC Us
2 | n.c.
3 | GND
4 | Output A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
extended temperature range

ER2008-0022 | 8-channel digital output 24 V DC, IMAX = 0.5 A (∑ 4 A)

The ER2008-0022 EtherCAT Box with digital outputs connects the binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A each, although the total current is limited to 4 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 0.5 A current.

The signal state is indicated by means of light emitting diodes. The signals are connected via M12 screw type connectors. All outputs are short-circuit-proof and protected against inverse connection.

The EtherCAT Box modules with zinc die-cast housing are ready for use in harsh industrial and process environments. With the fully sealed design and metal surfaces the ER series is ideal for applications requiring enhanced load capacity and protection against weld spatter, for example.

Technical data ER2008-0022
Number of outputs 8
Output connections M12, screw type
Protocol EtherCAT
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof, total current max. 4 A
Short circuit current max. 1.5 A
Distributed clocks
Auxiliary power current typ. 20 mA + load
Current consumption from US (without sensor current) 130 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 outputs
Electrical isolation 500 V
Special features 1 output per M12 plug
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation
Accessories  
ZK1090-3xxx-xxxx Cables for EtherCAT signal in- and -output
ZK2000-6xxx-xxxx Cables for M12 I/O connection sockets
ZK2020-3xxx-xxxx Cables for M8 power supply
Related products  
EP2008-0022 EtherCAT Box, industrial housing, 8 digital outputs, 24 V DC, IMAX = 0.5 A (∑ 4 A), 1 output per M12 plug