Digital output
ER2028-000x
 
ER2028-0001 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 2 A (∑ 4 A)
ER2028-0001
Connector
assignment
I/O
connection
M8 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC Us
3 | GND
4 | Output
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
extended temperature range
ER2028-0002 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 2 A (∑ 4 A)
ER2028-0002
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC Us
2 | Output B
3 | GND
4 | Output A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
extended temperature range

ER2028-000x | 8-channel digital output 24 V DC, IMAX = 2 A (∑ 4 A)

The ER2028 EtherCAT Box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 2 A each, although the total current is limited to 4 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 2 A signal current.

The signal state is indicated by means of light emitting diodes. The signals are optionally connected via M8 (ER2028-0001) or M12 (ER2028-0002) screw type connectors. The outputs are short-circuit-proof and protected against inverse connection.

The EtherCAT Box modules with zinc die-cast housing are ready for use in harsh industrial and process environments. With the fully sealed design and metal surfaces the ER series is ideal for applications requiring enhanced load capacity and protection against weld spatter, for example.

Technical data ER2028-0001 ER2028-0002
Number of outputs 8
Output connections M8, screw type M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 2.0 A (short-circuit-proof) per channel
Short circuit current max. 7 A
Distributed clocks
Auxiliary power current typ. 20 mA + load
Current consumption from US (without sensor current) 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 outputs
Electrical isolation 500 V
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation
Related products  