Digital output
ER2028-1032
 
ER2028-1032 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 2.8 A (∑ 16 A)
ER2028-1032
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power OUT 
Power IN 
1 | + 24 V DC Us
2 | (Output A)
3 | Output GND
4 | Output A
5 | FE
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | GNDP
2 | GNDs
3 | FE
4 | + 24 V DC US
5 | + 24 V DC UP
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
extended temperature range

ER2028-1032 | 8-channel digital output 24 V DC, IMAX = 2.8 A (∑ 16 A)

The ER2028-1032 EtherCAT Box with digital outputs connects the binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 2.8 A each, although the total current is limited to 16 A.

The signal state is indicated by means of light emitting diodes. The signals are connected via M12 screw type connectors. All outputs are short-circuit-proof and protected against inverse connection.

The EtherCAT Box modules with zinc die-cast housing are ready for use in harsh industrial and process environments. With the fully sealed design and metal surfaces the ER series is ideal for applications requiring enhanced load capacity and protection against weld spatter, for example.

Technical data ER2028-1032
Number of outputs 8
Output connections M12, screw type
Protocol EtherCAT
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 2.8 A per channel, individually short-circuit-proof, total current max. 16 A
Short circuit current max. 14 A
Distributed clocks
Auxiliary power current typ. 20 mA + load
Current consumption from US (without sensor current) 130 mA
Power supply connection feed: 1 x 7/8" plug, 5-pin; downstream connection: 1 x 7/8" socket, 5-pin
Bit width in the process image 8 outputs
Electrical isolation 500 V
Special features 1 output per M12 plug, 16 A total current
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation
Accessories  
ZK1090-3xxx-xxxx Cables for EtherCAT signal in- and -output
ZK2000-6xxx-xxxx Cables for M12 I/O connection sockets
ZK2030-xxxx-xxxx, ZK2031-xxxx-xxxx Cables for 7/8" power supply