Digital combi
ER2318-000x
 
ER2318-0001 | 4 x digital input + 4 x digital output 24 V DC, I<sub>max</sub> = 0.5 A, 10 µs
ER2318-0001
Connector
assignment
I/O
connection
M8 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC UP
3 | GND
4 | In-/Output
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
Outputs
Inputs
extended temperature range
ER2318-0002 | 4 x digital input + 4 x digital output 24 V DC, I<sub>max</sub> = 0.5 A, 10 µs
ER2318-0002
Connector
assignment
I/O
connection
M12 I/O
connection sockets 
Signal status display 
Labelling areas 
Power supply
status display:
Box supply (US
Auxiliary voltage (UP
Power supply feed 
Power supply down- 
stream connection
1 | + 24 V DC UP
2 | In-/Output B
3 | GND
4 | In-/Output A
5 | n.c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
EtherCAT
signal input 
EtherCAT
signal output 
Outputs
Inputs
extended temperature range

ER2318-000x | 4 x digital input + 4 x digital output 24 V DC, Imax = 0.5 A, 10 µs

The ER2318 EtherCAT Box combines four digital inputs and four digital outputs in one device. The outputs handle load currents of up to 0.5 A, are short-circuit-proof and protected against inverse polarity. The state of each signal is indicated by means of light emitting diodes. The signals are connected optionally via screw type M8 connectors (ER2318-0001) or connector M12 screw type (ER2318-0002).

The EtherCAT Box modules with zinc die-cast housing are ready for use in harsh industrial and process environments. With the fully sealed design and metal surfaces the ER series is ideal for applications requiring enhanced load capacity and protection against weld spatter, for example.

Technical data ER2318-0001 ER2318-0002
Specification EN 61131-2, type 1/3
Number of channels 4 inputs + 4 outputs
Input/output connections M8, screw type M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type
Input filter 10 µs
“0“ signal voltage -3…+5 V
“1“ signal voltage 11…30 V, 6 mA input current (EN 61131-2, type 3)
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Load type ohmic, inductive, lamp load
Rated load voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A
Short circuit current typ. 1.5 A
Auxiliary power current typ. 20 mA per channel
Current consumption from US 120 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 4 inputs + 4 outputs
Electrical isolation control voltage/fieldbus: yes
Operating/storage temperature -25…+60 °C/-40…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL in preparation