Digital input
IE10xx
 
IE1000, IE1001, IE1002, IE1010, IE1011, IE1012 | 8-channel digital input 24 V DC
IE1000
IE1001
IE1002
IE1010
IE1011
IE1012
Connector
assignment
I/O
connection
8 mm I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
M8
M12
1 | + 24 V DC Us
3 | GND
4 | Input
1 | + 24 V DC Us
2 | Input B
3 | GND
4 | Input A
5 | n.c.
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE100x, IE101x | 8-channel digital input 24 V DC

The IE10xx digital input modules acquire the binary control signals from the process level and transmit them to the higher-level automation unit. The state of the signals is indicated by light emitting diodes. The signals are optionally connected via 8 mm snap type (IE1000, IE1010), M8 (IE1001, IE1011) or M12 (IE1002, IE1012) screw type connectors. These versions are distinguished by input filters of different speeds.

The sensors are supplied from the box supply voltage US. The auxiliary voltage UP is not used in the input module, but may be connected in order to be relayed downstream.

Technical data IE1000 IE1001 IE1002
Number of inputs 8
Input connections 8 mm, snap type M8, screw type M12, screw type
Nominal input voltage 24 V DC (-15 %/+20 %)
Input filter 3.0 ms
“0“ signal voltage -3…+5 V (EN 61131-2, type 2)
“1“ signal voltage 11…30 V (EN 61131-2, type 2)
Input current typ. 6 mA (EN 61131-2, type 2)
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 inputs
Current consumption from US (without sensor current) 25 mA
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL
Technical data IE1010 IE1011 IE1012
Number of inputs 8
Input connections 8 mm, snap type M8, screw type M12, screw type
Nominal input voltage 24 V DC (-15 %/+20 %)
Input filter 0.2 ms
“0“ signal voltage -3…+5 V (EN 61131-2, type 2)
“1“ signal voltage 11…30 V (EN 61131-2, type 2)
Input current typ. 6 mA (EN 61131-2, type 2)
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 inputs
Current consumption from US (without sensor current) 25 mA
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL