Digital input
IE1502
 
IE1502 | 2-channel up/down counter 24 V DC, 100 kHz
IE1502
Connector
assignment
I/O
connection
M12 I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
Output
1 | + 24 V DC Us
2 | + 24 V Out 2
3 | GND
4 | + 24 V Out 1
5 | Shield
Gate signal
1 | + 24 V DC Us
2 | Gate 2
3 | GND
4 | Gate 1
5 | Shield
Counter connection
1 | + 24 V DC Us
2 | Clock 2
3 | GND
4 | Clock 1
5 | Shield
Up/down
1 | + 24 V DC Us
2 | Up/Down 2
3 | GND
4 | Up/Down 1
5 | Shield
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE1502 | 2-channel up/down counter 24 V DC, 100 kHz

The counter module has two fast counters running at up to 100 kHz. It counts binary pulses and transmits the counter state to the higher-level automation unit. The up/down input allows the counters to be switched between upwards and downwards counting (in 32 bits). The gate signals (gate inputs) allow the counters to be triggered: Depending on the level at the gate input, the counting function is halted or enabled. The outputs can be switched according to the counter state, and can therefore be used as fast control signals for field devices. From the controller it is possible to set the counter state, to start or halt the counter function, and to set the outputs. The signal state of the inputs and outputs is indicated by light emitting diodes.

Technical data IE1502
Number of inputs 2 counter inputs + 2 gate inputs + 2 up/down switches
Number of counters 2, each with a depth of 32 bits
Counting frequency 100 kHz (2 kHz for switching between up and down)
Signal connection M12, screw type
Nominal input voltage 24 V DC (-15 %/+20 %)
“0“ signal voltage -3…+5 V (EN 61131-2, type 2)
“1“ signal voltage 11…30 V (EN 61131-2, type 2)
Number of outputs 2 x 24 V DC, 0.5 A, individually short-circuit-proof
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 80 inputs/outputs: 2 x 32 bit data (2 x 8 bit control/status)
Current consumption from US (without sensor current) 25 mA
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL