Analog output
IE4112
 
IE4112 | 4-channel analog output 0/4…20 mA
IE4112
Connector
assignment
I/O
connection
M12 I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
1 | Output +
2 | +24 V DC UP
3 | Output -
4 | GNDP
5 | Shield
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE4112 | 4-channel analog output 0/4…20 mA

The IE4112 analog output module generates analog output signals in the range from 0/4 to 20 mA. The power is supplied to the process level with a resolution of 15 bits (default), and is electrically isolated. If the input is transmitted without an arithmetical sign, 16 bit resolution may also be selected. If necessary, the output scaling can be altered.

Ground potential for the four output channels is common with the 24 V DC supply. The analog actuators are powered by the load voltage. The applied load voltage (which can be any value up to 30 V DC) is fed through to supply the actuators.

Technical data IE4112
Number of outputs 4
Output connections M12, screw type
Signal current 0/4…20 mA
Nominal voltage 24 V DC (-15 %/+20 %)
Load < 500 Ω
Resolution 15 bit, configurable to 16 bit
Conversion time < 4 ms
Measuring error < ±0.1 % (relative to full scale value)
Actuator supply from the auxiliary voltage UP
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image output: 4 x 16 bit data (4 x 8 bit control/status optional)
Electrical isolation channels/control voltage: yes, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Current consumption from US (without sensor current) 40 mA
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL