Analog output
IE4132
 
IE4132 | 4-channel analog output ±10 V
IE4132
Connector
assignment
I/O
connection
M12 I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
1 | Output +/-
2 | +24 V DC UP
3 | Output GND
4 | GNDP
5 | Shield
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE4132 | 4-channel analog output ±10 V

The IE4132 analog output module generates analog output signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits, and is electrically isolated. If necessary, the output scaling can be altered.

Ground potential for the four output channels is common with the 24 V DC supply. The analog actuators are powered by the control voltage. The applied load voltage (which can be any value up to 30 V DC) is available for supply of the actuators.

Technical data IE4132
Number of outputs 4
Output connections M12, screw type
Signal current -10/0…10 V
Nominal voltage 24 V DC (-15 %/+20 %)
Load > 5 kΩ
Resolution 16 bit (incl. sign)
Conversion time < 4 ms
Measuring error < ±0.1 % (relative to full scale value)
Actuator supply from the auxiliary voltage UP
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image output: 4 x 16 bit data (4 x 8 bit control/status optional)
Electrical isolation channels/control voltage: yes, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Current consumption from US (without sensor current) 40 mA
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL