EtherNet/IP
 
IL230x-B905 | Fieldbus Box modules for EtherNet/IP
Coupler Box
IL230x-B905
Connector assignment
Module or IP-Link status display
Fieldbus connection
M12 socket
Fieldbus status display
3 types of connection
1 | 8 mm snap type connector
2 | M8 screw type connector
3 | M12 screw type connector
Power supply feed
Power supply downstream
connection
 IP-Link interface
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
1 | Tx+
2 | Rx+
3 | Tx-
4 | Rx-
Housing | Shield

IL230x-B905 | Fieldbus Box modules for EtherNet/IP

The IL230x-B905 Fieldbus Coupler Box connects EtherNet/IP with the modular Extension Box modules. A configuration consists of a Coupler Box and up to 120 different Extension Box modules. The Coupler Box automatically detects the connected extensions and allocates the inputs/outputs to the process image words.

The IL230x-B905 EtherNet/IP Coupler Box has a D-coded M12 connection. The IP address is set via a rotary switch (offset from a freely selectable start address). In networks with DHCP (a service for the allocation of the logical IP address to the physical node address [MAC-ID]), the Fieldbus Box obtains its IP address from the DHCP server.

 

Configuration

The IP address and other Ethernet parameters are set via two rotary selection switches. Special I/O parameters, for example the type of thermocouple that is used, can be set via KS2000.

 

Diagnostics

The extensive diagnostic functions of the Beckhoff devices allow rapid fault localisation. Diagnostic messages are transmitted via Ethernet and collected by the master. LEDs on the module indicate the status of the network connection, the device status, the status of the inputs and outputs and of the power supply.

 

Coupler Box

The EtherNet/IP Coupler Box gathers the I/O data from the Extension Box modules over the interference-free IP-Link optical fibre cable. It detects the connected modules and automatically allocates the input and output data to the process image. The Coupler Box has four digital inputs and four digital outputs; all other signal types are available in the form of an Extension Box.

System data EtherNet/IP | IL230x-B905
Number of I/O stations only limited by the IP address range
Number of I/O points depending on controller
Data transfer medium 2 x 2 twisted pair; CAT 5 (100 Mbaud)
Distance between stations 100 m (between hub/switch and IL230x-B905)
Data transfer rates 10/100 Mbaud, auto baud
Topology star over Ethernet hub or Ethernet Switch
Technical data IL230x-B905
Extension modules max. 120 with max. 512 byte input and 512 byte output data
Digital peripheral signals max. 512 inputs and 512 outputs
Analog peripheral signals max. 127 inputs and 127 outputs
Protocol EtherNet/IP
Configuration possibility via KS2000
Data transfer rates 10/100 Mbaud, automatic recognition of the transmission rate
Bus interface 1 x M12 socket, 4-pin (D-coded)
Power supply control voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Box supply current typ. 150 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current according to I/O type
Electrical isolation control voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type
Weight approx. 250 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL
Accessories  
KS2000 configuration software for extended parameterisation
Cordsets cordsets and connectors
Further information  
EtherNet/IP EtherNet/IP solutions in IP 20 and IP 67
System  
EtherNet/IP For further EtherNet/IP products please see the system overview.

Coupler Box

The Coupler Box for EtherNet/IP has four digital inputs and four digital outputs, optionally with snap type 8 mm diameter connectors, screw type M8 or screw type M12 connectors. Up to 120 Extension Box modules can be connected via the IP-Link communication facility.

IL230x-B905 Coupler Box for EtherNet/IP systems Plug
Digital combi
IL2300-B905 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A 8 mm
IL2301-B905 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M8
IL2302-B905 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M12

System overview