RS232
 
IPxxxx-B810, IL230x-B810, IL230x-C810 | Fieldbus Box modules for RS232
Compact Box
IPxxxx-B810
Coupler Box | PLC
IL230x-B810 | C810
Connector assignment
Module or IP-Link status display
Address selection switch
Fieldbus connection
Fieldbus status display
Configuration interface
3 types of connection
1 | 8 mm snap type connector
2 | M8 screw type connector
3 | M12 screw type connector
(Special functions:
M23 screw type connector)
Power supply feed
Power supply downstream
connection
 IP-Link interface
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
RS485
1 | + 5 V DC
2 | TxD
3 | GND
4 | RxD
5 | Shield
RS232
1 | n.c.
2 | TxD
3 | GND
4 | RxD
5 | Shield

IPxxxx-, IL230x-B/C810 | Fieldbus Box modules for RS232

 

KS8000

The KS8000 communication library for Windows 2000/XP is available for communication with the Fieldbus Box modules. The library offers functions with which it is possible to establish a simple connection from PC applications via the serial PC interface to the Fieldbus Box modules. The OCX interface can be utilised within any programming language that works with the specifications of the Component Object Model (COM) from Microsoft (e.g. Visual Basic, Visual C, Delphi, Java, etc.). The KS8000 library also has a DLL interface for any other C/C++ programs. KS8000 LV also makes an interface available for the graphical programming system LabVIEW from National Instruments.

 

Multiplexer function

As an additional operating mode, autonomous master/slave communication can be established between two serial Fieldbus Box modules. The input data from one device are copied directly to the outputs of the other, without the aid of an additional master – and vice versa. This kind of communication does not require any extensive configuration – it is only necessary for the node addresses to be appropriately selected.

 

Configuration

The node address is set in the range from 1 to 69 using two decimally coded rotary switches. The transmission rate is set to 38,400 baud by default. Like the other system parameters, it can be altered if required using the KS2000 software tool through the serial configuration interface of the Fieldbus Box.

 

Diagnostics

A status byte is transmitted with each telegram, providing information about the node and communication states. The status of the network connection, the device status, the status of the inputs and outputs and of the power supply are displayed by LEDs.

 

Compact Box

Compact Box modules with serial interfaces are available for all relevant industrial signals. In addition to digital and analog input and output modules including thermo­couple and RTD inputs, there are also incremental encoder interfaces available for displacement and angle measurement in addition to serial interfaces to solve a large number of communication tasks.

 

Coupler Box

The serial Coupler Box gathers the I/O data from the Extension Box modules over the interference-free IP-Link fibre optic cable. It detects the connected modules and automatically allocates the input and output data to the process image. Both data consistency and a clear separation of input and output data are ensured. The Coupler Box has four digital inputs and four digital outputs. Other kinds of signals are available in the Extension Box.

 

PLC Box

The PLC Box is an intelligent RS232 coupler that can perform non-central decentralised processing of I/O data and execute control tasks. It has four digital inputs and four digital outputs. Up to 120 further Extension Box modules can be connected via IP-Link. The I/O data can be made available either to the local PLC program or to the supervising controller. The PLC Box is programmed using TwinCAT through the configuration interface.

System data RS232 | IPxxxx-B810, IL230x-B810, IL230x-C810
Number of I/O stations 1 (peer-to-peer connection)
Number of I/O points depending on controller
Data transfer medium shielded copper cable, 2 x 0.25 mm²
Cable length 15 m
Data transfer rates 9.6 kbaud, 19.2 kbaud, 38.4 kbaud (default)
Software tool KS8000: provides ActiveX control, DLL and LabView interfaces for Windows NT/2000/XP
Technical data IPxxxx-B810 IL230x-B810, IL230x-C810
Extension modules max. 120 with max. 512 byte input and 512 byte output data
Digital peripheral signals according to I/O type max. 960 inputs and 960 outputs
Analog peripheral signals according to I/O type max. 252 inputs and 252 outputs
Protocol open, documented protocol
Configuration possibility via KS2000
Bus interface 1 x M12 socket, 5-pin, B-coded
Power supply control voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Box supply current 45 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current according to I/O type
Electrical isolation control voltage/fieldbus: yes, control voltage/inputs or outputs: according to I/O type
Weight approx. 210 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL
Accessories  
KS2000 configuration software for extended parameterisation
KS8000 Active-X control, DLL and LabView interface
TX1200 programming system conforms to IEC 61131-3
Cordsets cordsets and connectors
System  
RS232 For further RS232 products please see the system overview.
 

Compact Box

The Compact Box modules for RS232 offer a wide range of I/O functionalities. All relevant industrial signals are supported. The digital inputs and outputs can be connected either with snap type 8 mm diameter plugs, screw type M8 or M12 connectors. For analog signals the M12 version is used.

IPxxxx-B810 Compact Box for RS232 systems Plug
Digital input
IP1000-B810 Compact Box, 8 digital inputs 24 V DC, 3.0 ms filter 8 mm
IP1001-B810 Compact Box, 8 digital inputs 24 V DC, 3.0 ms filter M8
IP1002-B810 Compact Box, 8 digital inputs 24 V DC, 3.0 ms filter M12
IP1010-B810 Compact Box, 8 digital inputs 24 V DC, 0.2 ms filter 8 mm
IP1011-B810 Compact Box, 8 digital inputs 24 V DC, 0.2 ms filter M8
IP1012-B810 Compact Box, 8 digital inputs 24 V DC, 0.2 ms filter M12
IP1502-B810 Compact Box, 2 up/down counter, 24 V DC, 100 kHz M12
Digital output
IP2000-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 0.5 A 8 mm
IP2001-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 0.5 A M8
IP2002-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 0.5 A M12
IP2020-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) 8 mm
IP2021-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M8
IP2022-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M12
IP2040-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 12 A) 8 mm
IP2041-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 12 A) M8
IP2042-B810 Compact Box, 8 digital outputs 24 V DC, IMAX = 2 A (∑ 12 A) M12
IP2512-B810 Compact Box, 2 digital pulse width outputs 24 V DC, IMAX = 2.5 A M12
Digital combi
IP2300-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A 8 mm
IP2301-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A M8
IP2302-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A M12
IP2310-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A 8 mm
IP2311-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A M8
IP2312-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 0.5 A M12
IP2320-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) 8 mm
IP2321-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M8
IP2322-B810 Compact Box, 4 digital inputs 24 V DC, 3 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M12
IP2330-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) 8 mm
IP2331-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M8
IP2332-B810 Compact Box, 4 digital inputs 24 V DC, 0.2 ms filter, 4 digital outputs 24 V DC, IMAX = 2 A (∑ 4 A) M12
IP2400-B810 Compact Box, 16 digital combination inputs/outputs 24 V DC, 3 ms filter, IMAX = 0.5 A 8 mm
IP2401-B810 Compact Box, 16 digital combination inputs/outputs 24 V DC, 3 ms filter, IMAX = 0.5 A M8
Analog input
IP3102-B810 Compact Box, 4 differential analog inputs ±10 V, 16 bit M12
IP3112-B810 Compact Box, 4 differential analog inputs 0/4…20 mA, 16 bit M12
IP3202-B810 Compact Box, 4 analog inputs for resistance thermometer (RTD), PT100…1000, Ni100, 16 bit M12
IP3312-B810 Compact Box, 4 analog inputs for thermocouple, types J, K, L, B, E, N, R, S, T, U, 16 bit M12
Analog output
IP4112-B810 Compact Box, 4 analog outputs 0/4…20 mA, 16 bit M12
IP4132-B810 Compact Box, 4 analog outputs ±10 V, 16 bit M12
Special functions
IP5009-B810 Compact Box, 1 SSI encoder interface M23
IP5109-B810 Compact Box, 1 incremental encoder interface with complementary inputs, 1 MHz M23
IP5209-B810 Compact Box, 1 SinCos encoder interface, 1 VSS M23
IP6002-B810 Compact Box, 1 serial interface RS232C M12
IP6012-B810 Compact Box, 1 serial interface, 0…20 mA (TTY) M12
IP6022-B810 Compact Box, 1 serial interface, RS422, RS485 M12

Coupler Box

The Coupler Box for RS232 has four digital inputs and four digital outputs, optionally with snap type 8 mm diameter connectors, screw type M8 or M12 connectors. Up to 120 Extension Box modules can be connected via the IP-Link communication facility.

IL230x-B810 Coupler Box for RS232 systems Plug
Digital combi
IL2300-B810 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A 8 mm
IL2301-B810 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M8
IL2302-B810 Coupler Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M12

PLC Box

The PLC Box for RS232, programmable in accordance with IEC 61131-3, has four digital inputs and four digital outputs, optionally with snap type 8 mm diameter connectors, screw type M8 or screw type M12 connectors. Up to 120 Extension Box modules can be connected via the IP-Link communication facility.

IL230x-C810 PLC Box with controller IEC 61131-3 for RS232 systems Plug
Digital combi
IL2300-C810 PLC Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A 8 mm
IL2301-C810 PLC Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M8
IL2302-C810 PLC Box, 4 digital inputs 24 V, 3 ms filter, 4 digital outputs 24 V, 0.5 A M12

System overview